PCA Reference Data and Services
Toggle Dark/Light/Auto modeToggle Dark/Light/Auto modeToggle Dark/Light/Auto mode

Area duct & and instrumentation diagrams (D&ID)

A class with identifier http://rds.posccaesar.org/ontology/plm/rdl/PCA_100006095

MetadataThis section provides information about 'PCA_100006095' itself.

Source ontologynorsok-z001
CommentThe complete Area Duct & and Instrumentation Diagrams (D&ID) shall be in accordance with the plants’ process typicals and drafting standard.

The level of detail within packages shall be identical to that outside. Tag number shall be shown for all tagged components including manual valves.

Area Duct & Instrumentation Diagram (D&ID) shall be provided by area and include the following information:

  • All relevant HVAC system within the defined area;
  • All HVAC equipment with their tag number and all HVAC bulk items with their item number;
  • Equipment data summary with tag number for all equipment such as filters, fans, coils, etc.;
  • All ductwork identified with system no., sizes, duct classes, insulation classes;
  • All inline equipment;
  • Air flow to all serviced areas;
  • Area breaks and duct class breaks;
  • All areas/rooms served to be identified;
  • All instrument locations shall be indicated and completed with tag numbers;
  • Connections to other systems e.g. sea water, heating, cooling, drain, etc.;
  • Airflow in and out of diagram with references;
  • Fire partitions with fire rating.
NORSOK Z-001 interests stakeholder categoryheating, ventilating, and air conditioning
NORSOK Z-001 describes structural elementHVAC
NORSOK Z-001 definitionThe complete Area Duct & and Instrumentation Diagrams (D&ID) shall be in accordance with the plants’ process typicals and drafting standard.

The level of detail within packages shall be identical to that outside. Tag number shall be shown for all tagged components including manual valves.

Area Duct & Instrumentation Diagram (D&ID) shall be provided by area and include the following information:

  • All relevant HVAC system within the defined area;
  • All HVAC equipment with their tag number and all HVAC bulk items with their item number;
  • Equipment data summary with tag number for all equipment such as filters, fans, coils, etc.;
  • All ductwork identified with system no., sizes, duct classes, insulation classes;
  • All inline equipment;
  • Air flow to all serviced areas;
  • Area breaks and duct class breaks;
  • All areas/rooms served to be identified;
  • All instrument locations shall be indicated and completed with tag numbers;
  • Connections to other systems e.g. sea water, heating, cooling, drain, etc.;
  • Airflow in and out of diagram with references;
  • Fire partitions with fire rating.
skos:broadMatchflow information
skos:broaderDiagram

ConstraintsThis section lists constraints that members of 'PCA_100006095' shall satisfy.

ContextThis section provides super- and subtypes as well as members of 'PCA_100006095'.