Electrical load list
A class with identifier
http://rds.posccaesar.org/ontology/plm/rdl/PCA_100006179
Source ontology | norsok-z001 |
Comment | An electrical load list shall be worked out based on the Main Equipment List and emergency and/or essential consumers clearly marked as such in the list. Load list shall include individual consumers on high and low voltage switchboards (motor control centers) as well as assumed sum load on 400/230 V level. Sum UPS load per UPS system shall be listed. Allowance and contingency requirements for the load list shall be applied. |
NORSOK Z-001 rationale | See requirements to load study, ref. (Z-001-0052 - Electrical calculations / analyses). The purpose of this document is to define the electrical loading of the electrical power system. |
NORSOK Z-001 interests stakeholder category | electrical engineering |
NORSOK Z-001 describes structural element | Main power (u =or >6.6 kV) |
Main power (1.0 kV< u < 6.6 kV) | |
Emergency power (u<1.0 kV) | |
Main power (u = or <1.0 kV) | |
Battery and no-break | |
Emergency power (u = or >1.0 kV) | |
NORSOK Z-001 definition | An electrical load list shall be worked out based on the Main Equipment List and emergency and/or essential consumers clearly marked as such in the list. Load list shall include individual consumers on high and low voltage switchboards (motor control centers) as well as assumed sum load on 400/230 V level. Sum UPS load per UPS system shall be listed. Allowance and contingency requirements for the load list shall be applied. |
skos:broadMatch | items listing |
objects listing | |
skos:broader | List/Index |