Comment | Below are examples of expected level of detail. One or more examples may apply.
For Mechanical equipment:
- Dimensions
- Location and identification of piping and main components
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Thermal expansion effect, when relevant
- On the structural steel drawings, critical welds shall be included with a weld
identification number serving as a cross-reference to the weld summary index
- Obstacles from other disciplines shall be included when relevant
- Total weight, wet and dry and in operational condition
- Weights, centre of gravity and main dimensions of disassembled units/components
over 25 kg. Lifting lugs and runway beam for disassembling and their location shall
be shown
- Identification and location of all nozzle and external pipe connections as well as
requirements for flexible connections and acceptable loads and moments. Locations
shall be dimensioned and tolerances shown, if necessary in separate drawings
- Identification and location of all external electrical and control monitoring connections
(may be given in separate drawings describing the electrical arrangement and
instrumentation)
- For pressure equipment: for projects at locations where EU regulations for pressure
equipment apply, Category and Module shall be according to 2014/68/EU (PED)
- Include bolt tension requirements for pressure equipment flanges
- Iidentification of lubrication points
- Foundation information shall include:
- The outer dimensions and footprint of the support frame or foundation supports
- The size, grade and location of the foundation bolts and torque where this is
necessary
- Forces and moments transferred to load bearing structures, both under normal
operation and extreme conditions
- Details for adjustment and alignment
- Details for cut-outs inside outer limit of foundation
- Details for vibration dampening units (if installed) For Electrical equipment: - Panel equipment layout - position of modules, cards, vacant slots and other
information necessary for expansion or installation of new equipment in the same
cabinet
- Internal layout showing arrangement of auxiliary modules, cable trunks, etc.
- All equipment including junction boxes, push buttons, light fittings, socket outlets, etc.
- Dimensions
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Possible thermal expansion
- Obstacles from other disciplines shall be included when relevant
For Instrument equipment: - Dimensions
- Location and identification of piping and main components
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Possible thermal expansion
- Obstacles from other disciplines shall be included when relevant
- Panel equipment layout - position of modules, cards, vacant slots and other
information necessary for expansion or installation of new equipment in the same
cabinet
- Internal/back layout showing arrangement of auxiliary modules, cable trunks, etc.
- All equipment including technical network cabinets, junction boxes, push buttons,
light fittings, socket outlets, etc.
- Reference to part list/SPIR
For Telecom equipment:
A detailed drawing of the equipment shall be delivered. The drawing shall be to scale with
dimensions included.
For Panel/cabinet/rack the following shall be included in addition: - Position of modules, cards, vacant slots and other information necessary for
expansion or installation of new equipment in the same cabinet/rack
- Internal/back layout showing arrangement of auxiliary modules, cable trunks, etc.
For HVAC equipment: - Dimensions
- Location and identification of piping, ducting, MCTs (Multi core transit) and main
components
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Possible thermal expansion
- Obstacles from other disciplines shall be included when relevant
Foundation information shall include:
- The outer dimensions and footprint of the support frame or foundation supports
- The size, grade and location of the foundation bolts and torque where this is
necessary
- Forces and moments transferred to load bearing structures, both under normal
operation and extreme conditions
- Details for adjustment and alignment
- Details for cut-outs inside outer limit of foundation
- Details for vibration dampening units (if installed)
For Lifting appliances:
General arrangement drawing of complete unit and foundation: - Dimensions
- Location of centre of gravity
- Total weight in operational condition
Foundation:
- The outer dimensions and footprint of the support frame or foundation
support
- The size, grade and location of the foundation bolts and torque where this is
necessary
- Forces and moments transferred to load bearing structures, both under
normal operation and extreme conditions
- Details for adjustment and alignment
General arrangement drawing for Crane cabin, machinery room, winches, crane boom,
slewing drives, main drive, hook block, wire sheave arrangements, etc.:
- Dimensions
- Location and identification of bolting, piping and main components
- Location of centre of gravity
- Total weight in operational condition
General arrangement drawing for inspections for primary steel structures e.g.
pedestal/foundation, crane boom/traverse beams, A-frame, runway beams, winches, hook
block, etc.
- Critical welds shall be included with a weld identification number including weld
classification. NDT procedures and intervals for each weld classification shall be
included.
For Well completion equipment:
Electrical submergible pump (ESP) - Dimensions
- Weights, centre of gravity and main dimensions of disassembled
units/components over 25 kg
Wellhead penetrator
- Dimensions
- Necessary space for disassembly and maintenance
- Obstacles from other disciplines shall be included when relevant
- All equipment including technical network cabinets, junction boxes, push buttons,
light fittings, socket outlets, etc.
- Parts list
|
NORSOK Z-001 definition | Below are examples of expected level of detail. One or more examples may apply.
For Mechanical equipment:
- Dimensions
- Location and identification of piping and main components
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Thermal expansion effect, when relevant
- On the structural steel drawings, critical welds shall be included with a weld
identification number serving as a cross-reference to the weld summary index
- Obstacles from other disciplines shall be included when relevant
- Total weight, wet and dry and in operational condition
- Weights, centre of gravity and main dimensions of disassembled units/components
over 25 kg. Lifting lugs and runway beam for disassembling and their location shall
be shown
- Identification and location of all nozzle and external pipe connections as well as
requirements for flexible connections and acceptable loads and moments. Locations
shall be dimensioned and tolerances shown, if necessary in separate drawings
- Identification and location of all external electrical and control monitoring connections
(may be given in separate drawings describing the electrical arrangement and
instrumentation)
- For pressure equipment: for projects at locations where EU regulations for pressure
equipment apply, Category and Module shall be according to 2014/68/EU (PED)
- Include bolt tension requirements for pressure equipment flanges
- Iidentification of lubrication points
- Foundation information shall include:
- The outer dimensions and footprint of the support frame or foundation supports
- The size, grade and location of the foundation bolts and torque where this is
necessary
- Forces and moments transferred to load bearing structures, both under normal
operation and extreme conditions
- Details for adjustment and alignment
- Details for cut-outs inside outer limit of foundation
- Details for vibration dampening units (if installed) For Electrical equipment: - Panel equipment layout - position of modules, cards, vacant slots and other
information necessary for expansion or installation of new equipment in the same
cabinet
- Internal layout showing arrangement of auxiliary modules, cable trunks, etc.
- All equipment including junction boxes, push buttons, light fittings, socket outlets, etc.
- Dimensions
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Possible thermal expansion
- Obstacles from other disciplines shall be included when relevant
For Instrument equipment: - Dimensions
- Location and identification of piping and main components
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Possible thermal expansion
- Obstacles from other disciplines shall be included when relevant
- Panel equipment layout - position of modules, cards, vacant slots and other
information necessary for expansion or installation of new equipment in the same
cabinet
- Internal/back layout showing arrangement of auxiliary modules, cable trunks, etc.
- All equipment including technical network cabinets, junction boxes, push buttons,
light fittings, socket outlets, etc.
- Reference to part list/SPIR
For Telecom equipment:
A detailed drawing of the equipment shall be delivered. The drawing shall be to scale with
dimensions included.
For Panel/cabinet/rack the following shall be included in addition: - Position of modules, cards, vacant slots and other information necessary for
expansion or installation of new equipment in the same cabinet/rack
- Internal/back layout showing arrangement of auxiliary modules, cable trunks, etc.
For HVAC equipment: - Dimensions
- Location and identification of piping, ducting, MCTs (Multi core transit) and main
components
- Necessary space for disassembly and maintenance
- Location of centre of gravity
- Possible thermal expansion
- Obstacles from other disciplines shall be included when relevant
Foundation information shall include:
- The outer dimensions and footprint of the support frame or foundation supports
- The size, grade and location of the foundation bolts and torque where this is
necessary
- Forces and moments transferred to load bearing structures, both under normal
operation and extreme conditions
- Details for adjustment and alignment
- Details for cut-outs inside outer limit of foundation
- Details for vibration dampening units (if installed)
For Lifting appliances:
General arrangement drawing of complete unit and foundation: - Dimensions
- Location of centre of gravity
- Total weight in operational condition
Foundation:
- The outer dimensions and footprint of the support frame or foundation
support
- The size, grade and location of the foundation bolts and torque where this is
necessary
- Forces and moments transferred to load bearing structures, both under
normal operation and extreme conditions
- Details for adjustment and alignment
General arrangement drawing for Crane cabin, machinery room, winches, crane boom,
slewing drives, main drive, hook block, wire sheave arrangements, etc.:
- Dimensions
- Location and identification of bolting, piping and main components
- Location of centre of gravity
- Total weight in operational condition
General arrangement drawing for inspections for primary steel structures e.g.
pedestal/foundation, crane boom/traverse beams, A-frame, runway beams, winches, hook
block, etc.
- Critical welds shall be included with a weld identification number including weld
classification. NDT procedures and intervals for each weld classification shall be
included.
For Well completion equipment:
Electrical submergible pump (ESP) - Dimensions
- Weights, centre of gravity and main dimensions of disassembled
units/components over 25 kg
Wellhead penetrator
- Dimensions
- Necessary space for disassembly and maintenance
- Obstacles from other disciplines shall be included when relevant
- All equipment including technical network cabinets, junction boxes, push buttons,
light fittings, socket outlets, etc.
- Parts list
|