Electrical load list

A class with identifier http://rds.posccaesar.org/ontology/plm/rdl/PCA_100006179

MetadataThis section provides information about 'PCA_100006179' itself.

Source ontology norsok-z001
Comment An electrical load list shall be worked out based on the Main Equipment List and emergency and/or essential consumers clearly marked as such in the list. Load list shall include individual consumers on high and low voltage switchboards (motor control centers) as well as assumed sum load on 400/230 V level. Sum UPS load per UPS system shall be listed. Allowance and contingency requirements for the load list shall be applied.
NORSOK Z-001 rationale See requirements to load study, ref. (Z-001-0052 - Electrical calculations / analyses). nThe purpose of this document is to define the electrical loading of the electrical power system.
NORSOK Z-001 interests stakeholder category electrical engineering
NORSOK Z-001 describes structural element Main power (u =or >6.6 kV)
Main power (1.0 kV< u < 6.6 kV)
Main power (u = or <1.0 kV)
Emergency power (u = or >1.0 kV)
Emergency power (u<1.0 kV)
Battery and no-break
NORSOK Z-001 definition An electrical load list shall be worked out based on the Main Equipment List and emergency and/or essential consumers clearly marked as such in the list. Load list shall include individual consumers on high and low voltage switchboards (motor control centers) as well as assumed sum load on 400/230 V level. Sum UPS load per UPS system shall be listed. Allowance and contingency requirements for the load list shall be applied.
skos:broadMatch objects listing
items listing
skos:broader List/Index