Equipment supplier piping and instrument diagram (P&ID)

A class with identifier http://rds.posccaesar.org/ontology/plm/rdl/PCA_100006190

MetadataThis section provides information about 'PCA_100006190' itself.

Source ontology norsok-z001
Comment Piping and Instrument Diagram (P&ID) includes the complete set of P&IDs, typicals and legends. Equipment supplier's drafting standard shall be used. Symbols used shall be described by a symbol legend on the P&ID, or as a separate document/drawing/P&ID sheet. All connections external to the supply shall be shown on the P&ID, marked with a unique number (N1, N2, etc.). Reference to the interfacing external P&IDs should also be given.nAll interface signals to and from the plant’s safety and automation systems shall be shown nwith reference to the interfacing external P&IDs. Control and monitoring functions shall be ndrawn on the P&ID, this also applies for control panel locally within the supply.nIdentical parallel items or systems shall be drawn in full detail, i.e. typical drawings with nassociated tag number tables are not acceptable.nUnique plant tags shall be used as assigned by the engineering contractor. Supplier’s ninternal tag numbers shall be shown in addition where required for use of supplier’s standardndocumentation, preferably by use of tables on the P&ID/separate P&ID sheet, linking unique nplant tag with supplier’s internal tag.
NORSOK Z-001 extended definition Context specific information to be added
NORSOK Z-001 interests stakeholder category instrumentation engineering
NORSOK Z-001 definition Piping and Instrument Diagram (P&ID) includes the complete set of P&IDs, typicals and legends. Equipment supplier's drafting standard shall be used. Symbols used shall be described by a symbol legend on the P&ID, or as a separate document/drawing/P&ID sheet. All connections external to the supply shall be shown on the P&ID, marked with a unique number (N1, N2, etc.). Reference to the interfacing external P&IDs should also be given.nAll interface signals to and from the plant’s safety and automation systems shall be shown nwith reference to the interfacing external P&IDs. Control and monitoring functions shall be ndrawn on the P&ID, this also applies for control panel locally within the supply.nIdentical parallel items or systems shall be drawn in full detail, i.e. typical drawings with nassociated tag number tables are not acceptable.nUnique plant tags shall be used as assigned by the engineering contractor. Supplier’s ninternal tag numbers shall be shown in addition where required for use of supplier’s standardndocumentation, preferably by use of tables on the P&ID/separate P&ID sheet, linking unique nplant tag with supplier’s internal tag.
skos:broadMatch flow information
skos:broader Diagram

ConstraintsThis section lists constraints that members of 'PCA_100006190' shall satisfy.